 DRAN120 SERIES
FOR DC BACKUP SYSTEM
AC - DC DIN RAIL MOUNTABLE 120W INDUSTRIAL CONTROL EQUIPMENT
FEATURES
COMPACT DESIGN SIMPLE IN APPLICATION LOW PRICING WORKABLE FOR BOTH POWER SUPPLY / DC BACKUP SYSTEM INPUT VOLTAGE 115/230VAC AUTO SELECT
SELECTION CHART
DRAN 120 - 24 A *
Wattage 12 : 13.6V OUT 24 : 27.2V OUT 48 : 54.5V OUT DC Backup System SCREW TERMINALS
MODEL LIST
MODEL NO. INPUT VOLTAGE
115 / 230 VAC 115 / 230 VAC 115 / 230 VAC
OUTPUT OUTPUT WATTAGE VOLTAGE Single Output Models
120 WATTS 120 WATTS 120 WATTS + 13.6 VDC + 27.2 VDC + 54.5 VDC
OUTPUT CURRENT
9A 4.4A 2.2A
EFF. (min.)
82% 84% 85%
EFF.1) (typ.)
84% 86% 87%
DRAN120-12A* DRAN120-24A* DRAN120-48A*
- - ++ Rdy
+
Rdy Rdy K1
- - ++ Rdy
+
K1 D1 K1 Fuse LOAD Rdy Rdy BATTERY
DRAN120 Series
D1
K1
Fuse LOAD
DRAN120 Series
BATTERY
DRAN120 Series For DC Backup System Application
DRAN120 Series For DC Backup System Application
Note 1.The suffix "*" is part of the model number, which specifies the product is designed and pre-trim for low-cost DC backup power system with external Lead-Acid battery, Relay and Fuse. 2.The manufacturer is liable neither for the external components nor the damage to the power supply causing by external components. 3.The total consumption current including loading and battery charging current should not exceed the maximum rated current of power supply. 4.The operation concept of DC backup power system A. When AC power alive The "Rdy" is close circuit to active the external Relay . The power supply feeds current into the external loads and charges through Relay to the external battery as well. B. When AC power interrupted The "Rdy" is remain close circuit to maintain the external Relay remain active, the external battery supply current to the external loads. C. When Battery power low The "Rdy" become open circuit and the external Relay become inactive to disconnect the battery from external loads.
www.chinfa.com 2008.03.28 sales@chinfa.com
FOR DC BACKUP SYSTEM
DRAN120 SERIES
min.
3,000 100 -25 -25 20 L123.6 x W63.2 x D123.6 + 71 2.5 + 85 95
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
GENERAL
Characteristics
Isolation voltage Isolation resistance Ambient temperature Derating Storage temperature Relative humidity Dimension Cooling Case material
Conditions
Input / Output Input / Output, @ 500VDC Operating at Vi nom Vi nom, from +61 to +71oC Non operational Vi nom, Io nom Screw terminal type Free air convection Metal
typ.
max.
unit
VAC M
o
C C
% / oC
o
% RH mm mm
INPUT SPECIFICATIONS
Characteristics
Rated input voltage Input voltage range Io nom Ta min ... T max, AC 115V selected a Io nom AC 230V selected DC Rated input current Line frequency Inrush current P F. C. . Io nom Vi nom, Io nom Vi nom, Io nom Vi : 230VAC, Io nom Vi : 115VAC Vi : 230VAC 0.7 47
Conditions
min.
90 186 210
typ.
max.
132 264 370
unit
VAC VAC VAC VDC A Hz A A
115 / 230 (auto select)
2.8 / 1.4 63 24 48
OUTPUT SPECIFICATIONS
Characteristics
Output voltage accuracy
(Adjusted before shipment)
Conditions
Vi nom, Io max Vi nom Io nom, Vi min ...Vi max Vi nom, Io min ...Io nom Vi nom, Io min Vi nom, Io nom,BW = 20MHz Vi nom, Io nom Vi nom, Io nom Vi = 115VAC Vi = 230VAC 12V models 24V models 48V models
min.
-0 0
typ.
max.
+1 0.5 1 0.3 50
unit
% % % % %/C mV ms ms
o
Minimum load Line regulation Load regulation Temperature coefficient Ripple & noise Hold up time Voltage trim range
16 25 30 11.4 22.5 45 10.4 21.2 42.8 10.3 21.1 42.7 14.5 28.5 55 11.4 22.2 43.8 11.3 22.1 43.7
VDC VDC VDC VDC VDC VDC VDC VDC VDC
Rdy Close / DC ON indicator threshold at start up
Vi nom, Io nom
12V models 24V models 48V models
Rdy Open / DC LOW indicator threshold after start up
Vi nom, Io nom
12V models 24V models 48V models
www.chinfa.com 2008.03.28
sales@chinfa.com
FOR DC BACKUP SYSTEM
DRAN120 SERIES
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
CONTROL AND PROTECTION
Characteristics
Input fuse Rated over load protection Over voltage protection Output short circuit Vi nom Vi nom, Io nom Vi nom, Io nom 105 125 Current limited
Conditions
min.
typ.
max.
125 145
unit
% %
T3.15A / 250VAC internal
APPROVALS AND STANDARDS
UL / cUL TUV CE UL508 Listed, UL60950-1 Recognized EN60950-1 EN61000-6-3, EN55022 class B, EN61000-3-2, EN61000-3-3 EN61000-6-2, EN55024
CIRCUIT SCHEMATIC
Block diagram for DRAN120 series
L Fuse Filter N Y
Inrush Current Limiter, Rectifier and Auto Select 115 / 230 Vac
Vo + P. F. C. Circuit
Smoothing Circuit Switching
Device
Rectifier
Current Detection
Vo -
PWM Controller
Opto Isolation Opto Isolation
Reference & Error Amp. Over Voltage Detection Output Level Detection
Vout ADJ.
(Green LED) (Red LED)
DC ON
DC LOW
(Relay Contact)
PHYSICAL CHARACTERISTICS
CASE SIZE
SCREW TERMINAL TYPE WEIGHT 123.6 x 63.2 x 123.6 mm 4.87 x 2.49 x 4.87 inches 920g
www.chinfa.com
2008.03.28
sales@chinfa.com
FOR DC BACKUP SYSTEM
DRAN120 SERIES
CONSTRUCTION
MECHANISM & PIN CONFIGURATION
mm [inch]
63.2 [2.49] 116.6 [4.59] 6.90 [0.27]
6
1
Easy snap-on mounting onto the DIN-Rail (TS35/7.5 or TS35/15), unit sits safeIy and firmly on the rail.
- - ++ Rdy Vout ADJ.
123.6 [4.87]
DC LO DC ON
INSTALLATION
Ventilation / Cooling Normal convection All sides 25mm free space For cooling recommended Connector size range Screw terminal: 10-24AWG flexible / solid cable, 8 m/m stripping at cable end recommends
DRAN120*
L N
7
9
PIN ASSIGNMENT
PIN NO.
1 2 3 4 5 6 7 8 9
Designation
RDY
Description
A normal open relay contact for DC ON level control (Never connect except 24V model) Positive output terminal Positive output terminal Negative output terminal Negative output terminal Ground this terminal to minimize high-frequency emissions Input terminals (phase conductor, no polarity at DC input) Input terminals (neutral conductor, no polarity at DC input) Operation indicator LED DC LOW voltage indicator LED Trimmer-potentiometer for Vout adjustment
OUT
V+ V+ VV-
IN
L N DC ON DC LO Vout ADJ.
DERATING
100 Power out [ % ] 75
0 -25
OTHER
61
71
www.chinfa.com
2008.03.28
sales@chinfa.com


▲Up To Search▲   

 
Price & Availability of DRAN120-12A

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X